3 Β· What Goes Wrong

What Goes Wrong

Common defects and what to do

What you find What it probably means What to do
Missing Used, moved or stolen Replace from spare stock, report to client
Obstructed / hidden Site housekeeping Ask site to clear it, record it, report if not fixed
Tamper seal broken, pin missing May have been partly discharged Weigh and check the gauge. If any agent is lost, recharge. Refit the pin and seal.
Gauge in the red (low) Slow leak, or partly used Recharge and find the leak (valve O-ring, gauge thread)
Gauge in the red (high) Overcharged, or exposed to heat Investigate. Do not leave in service until it's in range.
Gauge needle stuck Faulty gauge Replace the gauge, or the extinguisher
Weight low Agent lost (COβ‚‚ leaks through the valve) Recharge. For COβ‚‚, if the loss is beyond the permitted limit VERIFY, recharge.
Hose split, perished or blocked Age, UV, insects, damage Replace the hose
COβ‚‚ horn cracked or missing Damage Replace with the correct non-conductive horn
Dents, gouges, bulging Impact damage Condemn if the shell is weakened (see chart)
Corrosion (rust, pitting, especially around the base and welds) Wet or corrosive environment, common on chemical sites Light surface rust: clean and monitor. Pitting or corrosion at seams: condemn.
Caked powder (cartridge types, or found at discharge test) Moisture or vibration Replace the powder; find out why moisture is getting in
Label illegible or missing Weather or chemical attack Relabel if it can be positively identified, otherwise condemn
Overdue discharge / hydro test Missed service Carry out the test, or replace
Wrong type for the risk Layout changed, or it was wrong from the start Report to the client in writing. Don't just swap it without telling them.
Obsolete type Very old stock Remove from service (see below)

When to condemn

flowchart TD
  A["Defect found"] --> B{"Shell damaged?<br/>dents at seams, bulging,<br/>cracks, pitting, fire damage"}
  B -- Yes --> X["❌ CONDEMN<br/>Depressurise safely<br/>Mark 'condemned'<br/>Remove & replace"]
  B -- No --> C{"Failed a hydrostatic /<br/>pressure test?"}
  C -- Yes --> X
  C -- No --> D{"Obsolete type, or unlisted /<br/>not to a recognised standard?"}
  D -- Yes --> X
  D -- No --> E{"Parts available and<br/>economic to repair?"}
  E -- No --> X
  E -- Yes --> F["βœ” Repair / recharge<br/>re-check and return to service"]
Tip: on a phone, scroll sideways or rotate to landscape.

Obsolete types: take out of service

Both standards say very old designs must be removed. Examples you could still find on old sites:

  • Soda-acid and chemical foam extinguishers (operated by turning upside down)
  • Extinguishers with soft-soldered or riveted copper/brass bodies
  • Cast iron shells
  • Carbon tetrachloride / vaporising liquid (toxic)
  • COβ‚‚ extinguishers with metal horns NFPA. A metal horn conducts electricity, which is a shock risk on electrical fires.
  • Halon extinguishers BS. Banned in the UK and EU except for listed critical uses (e.g. some aircraft and military applications).

Real-world ways extinguishers fail

  • "It was there, but nobody could reach it." Blocked by stock, a locked cabinet, or moved.
  • Powder caked solid in extinguishers on vibrating plant or vehicles. It looks fine, the gauge is green, but nothing comes out. This is exactly what the BS discharge test and the NFPA internal exam are designed to catch.
  • Water extinguisher used on an electrical fire, or COβ‚‚ used in a small room: the wrong type for the risk. This is why siting and suitability are checked.
  • Gauge stuck in the green while the extinguisher is empty. Weighing catches it.
  • Corrosion from the outside in on chemical plants, often hidden at the base or under the bracket. Lift it and look underneath.

Key takeaways

  • Most defects come down to missing, used, leaking, blocked or corroded.
  • Damaged shell = condemn, no exceptions.
  • Report wrong type or wrong place in writing. The client must decide.
  • Lift it, weigh it, look underneath it. The gauge alone isn't enough.
✎ Draft – not yet technically reviewed. Check anything marked VERIFY against your copy of the standard.
Sources: BS 5306-3:2017; NFPA 10 (2022) ch. 7; industry experience