Working safely on site

Fire systems are designed to save lives, but servicing them has its own hazards. This page covers the hazards common to all equipment. Each module adds its own.

The main hazards

Hazard Where you'll meet it What can go wrong Control
Stored pressure Extinguishers, gas cylinders, pressurised pipework Parts or cylinders released at high force Depressurise before dismantling, never point a valve at anyone, use the correct tools
Water under pressure Sprinkler, deluge, hydrant, hose reel Pipework whipping, flooding, damage to stock or plant Know where the isolation valves are and open/close slowly
Accidental discharge Gas suppression, deluge, foam Room flooded with agent, people trapped, plant damage Mechanical and electrical isolation before work; follow the CTT exactly
Asphyxiation COβ‚‚ and inert gas protected rooms Unconsciousness and death in seconds at COβ‚‚ design concentrations Never enter after a discharge until ventilated and cleared; lock-off
Working at height Detectors, sprinkler heads, high-level valves Falls Right access equipment, inspected, with a permit if required
Manual handling Extinguishers (up to ~20 kg), cylinders (60 kg+) Back injuries Trolleys and cylinder trucks, team lifts
Hazardous substances Foam concentrate, powder, wet chemical Skin/eye irritation, inhalation COSHH data sheet, gloves, eye protection, dust control
Explosive atmospheres Chemical plant areas (ATEX zones) A spark from a tool or phone ignites flammable vapour Only certified equipment in zoned areas; hot work permit; gas testing
Live electricity Alarm panels, pump starters, release panels Shock Isolate and prove dead; only competent people work on mains

Permit to work, isolation and impairment

On an industrial site like Dow, you don't touch anything without a permit. A permit tells you:

  • exactly what you're allowed to work on,
  • what has been isolated, and by whom,
  • what hazards are present, and what PPE and gas tests are needed,
  • when it expires.
flowchart TD
  A["Need to work on a fire system"] --> B["Request permit from site"]
  B --> C["Site checks hazards<br/>Β· area classification<br/>Β· isolations<br/>Β· gas test if needed"]
  C --> D{"Will fire protection<br/>be impaired?"}
  D -- Yes --> E["Impairment procedure:<br/>notify control room, insurer if required,<br/>fire watch, tag the valve/panel"]
  D -- No --> F
  E --> F["Permit issued & signed<br/>you're briefed"]
  F --> G["Do ONLY the work on the permit"]
  G --> H["Restore Β· test Β· de-impair"]
  H --> I["Hand back & sign off permit"]
Tip: on a phone, scroll sideways or rotate to landscape.

What goes wrong: real-world patterns

  • Valve left closed after maintenance. The system looks fine but can't deliver water. This is the single biggest reason sprinklers fail to control fires.
  • Isolation not removed. An alarm zone stays disabled for weeks because nobody restored it.
  • Wrong item worked on. Two similar valves, wrong one isolated. Always confirm the tag/ID.
  • Accidental gas discharge during maintenance. Usually because the actuator wasn't removed or isolated first.
  • Records not completed. The next engineer doesn't know a defect was found.

Key takeaways

  • No permit, no work.
  • Know what you've isolated and put it back.
  • If anything doesn't match the permit or the drawing, stop and ask.
✎ Draft – not yet technically reviewed. Check anything marked VERIFY against your copy of the standard.
Sources: Health and Safety at Work etc. Act 1974; Work at Height Regulations 2005; COSHH 2002; DSEAR 2002